Omron CJ2 User Manual page 83

Cj series
Hide thumbs Also See for CJ2:
Table of Contents

Advertisement

CPU Unit Status Indicators
Indicators on front
of CPU Unit
The CJ2 CPU Unit status can be checked with the indicators at the top of the front panel of the Unit.
The following table describes these indicators.
Indicator
RUN
Green
ERR/ALM
Red
INH
Yellow
PRPHL
Yellow
COMM
Yellow
BKUP
Yellow
*1 Do not turn OFF the power supply to the PLC while this indicator is lit.
CJ2 CPU Unit Hardware User's Manual
Color
Status
ON
Lights when the PLC is operating normally in MONITOR or RUN
mode. The program is being executed.
Flashing
System download mode error or DIP switch settings error.
OFF
PLC has stopped operating while in PROGRAM mode, or has
stopped operating due to a fatal error, or is downloading data from
the system.
ON
A fatal error (including FALS(007) instruction execution) or a hard-
ware error (watchdog timer error) was found in self-diagnosis.
The CJ2 CPU Unit will stop operating, and the outputs from all
Output Units will turn OFF.
Flashing
A non-fatal error was found (including FAL(006) instruction execu-
tion) in the self-diagnosis.
The CJ2 CPU Unit will continue operating.
OFF
The CJ2 CPU Unit is operating normally.
ON
Output OFF Bit (A500.15) has been turned ON.
The outputs from all Output Units will turn OFF.
OFF
Output OFF Bit (A500.15) has been turned OFF.
Flashing
The CJ2 CPU Unit is communicating (sending or receiving) via the
peripheral (USB) port.
OFF
The CJ2 CPU Unit is not communicating via the peripheral (USB)
port.
Flashing
The CJ2 CPU Unit is communicating (sending or receiving) via the
serial port (RS-232C).
OFF
The CJ2 CPU Unit is not communicating via the serial port
(RS-232C).
ON
User program and parameter area data is being backed up to
flash memory in the CPU Unit or being restored from flash mem-
ory after the power supply to the PLC was turned ON.
OFF
Data is not being written to flash memory.
3 Nomenclature and Functions
7-segment display and
indicators for
EtherNet/IP port
(Refer to 3-1-2
Built-in EtherNet/IP Section.)
Meaning
3
*1
3-3

Hide quick links: