Omron CJ2 User Manual page 187

Cj series
Hide thumbs Also See for CJ2:
Table of Contents

Advertisement

Error Causes and Remedies
Suspected cause of
error
An error specific to the
Unit
Faulty connection at Unit
(at a connector)
Unit failure
Noise
• Data corruption in bus
signals
Special I/O Unit Error (Non-fatal Error)
A Special I/O Unit error occurs when there is an error in the data conversion between the CPU Unit and
a Special I/O Unit.
POWER
Lit.
Not lit.
*1 The exes (XX) indicate the unit number where the error occurred.
*2 The bit corresponding to the unit number where the error occurred turns ON.
Recovery Processing Flow
Special I/O Unit error
occurs.
Restart the Special I/O Unit.
Is the error cleared?
Restart the System.
CJ2 CPU Unit Hardware User's Manual
Confirmation method
Refer to the manual for the
particular Unit.
Check the insertion at the
connector. Restart the
Unit and check whether
the error is cleared.
If restarting the Unit does
not clear the error, check
whether the error is
cleared by replacing the
Unit.
Restart the CPU Unit and
check whether the error
occurs again.
RUN
ERR/ALM
Flashing.
Reset, or turn the power OFF and back ON.
No
Yes
Replace the Special I/O Unit.
Restart the Special I/O Unit.
Remedy
Same as at the left.
Tighten the screws.
Replace the applicable
Unit.
Take measures against
noise. (Investigate the
path of entry.)
• FG
• Power lines
CX-Program-
Error flag
mer display
Special IO
A402.06
Unit Error XX
*1
Check the Unit connections.
6 Troubleshooting
Prevention of recur-
rence
Same as at the left.
Check for vibration and
shock.
Same as at the left.
Same as at the left.
Error infor-
Error code
mation
0300 to 035F
A418 to A423
or 03FF
*2
6-21
6