CJ1W-OC211 Contact Output Unit (16 Points)
Name
Model
Max. Switching Capacity
Min. Switching Capacity
Relays
Service Life of Relay
ON Response Time
OFF Response Time
Number of Circuits
Insulation Resistance
Dielectric Strength
Internal Current Consumption
Weight
Circuit Configuration
Terminal Connections
*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
A-18
16-point Contact Output Unit with Terminal Block
CJ1W-OC211
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit)
1 mA 5 VDC
NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be
replaced.
Electrical: 150,000 operations (24 VDC, resistive load)/ 100,000 opera-
tions (250 VAC, cosφ = 0.4, inductive load)
Mechanical: 20,000,000 operations
Service life will vary depending on the connected load. Refer to page A-51
for information on service life according to the load.
15 ms max.
15 ms max.
16 points/common, 1 circuit
20 MΩ between external terminals and the GR terminal (500 VDC)
2,000 VAC between the external terminals and the GR terminal for
1 minute at a leakage current of 10 mA max.
110 mA 5 VDC max.
96 mA 24 VDC max. (6 mA × No. of ON points)
170 g max.
Output indicator
*1
Signal
Connec-
tor pin
name
OUT0
L
A0
B0
OUT2
L
A1
B1
OUT4
L
A2
B2
OUT6
L
A3
B3
OUT8
L
A4
B4
OUT10
L
A5
B5
OUT12
L
A6
B6
OUT14
L
A7
B7
COM
2 A 250 VAC,
A8
2 A 24 VDC max.
B8
Signal
name
OUT0
to
OUT15
COM
COM
Signal
name
OUT1
L
OUT3
L
OUT5
L
OUT7
L
OUT9
L
OUT11
L
OUT13
L
OUT15
L
COM