NEC SigmaBlade N8406-040(F) User Manual page 173

8g fc switch
Table of Contents

Advertisement

Checking Current Zoning
Type "cfgshow" command on the console screen.
1.
NOTE:
Any commands used on the switch console should be specified with lowercase letters.
The current zoning information appears.
2.
Without zoning information, skip to "Creating zone alias name" and following.
With some zoning information, recheck setting change to take proper action.
<No existence of zoning information>
ALE044120T2:admin> cfgshow
Defined configuration:
no configuration defined
Effective configuration:
no configuration in effect
ALE044120T2:admin>
<Existence of zoning information>
ALE044120T2:admin> cfgshow
Defined configuration:
cfg:
zone_cfg
zone:
zone1
zone:
zone2
Effective configuration:
cfg:
zone_cfg
zone:
zone1
zone:
zone2
ALE044120T2:admin>
IMPORTANT:
If enabled zoning information appears, take note on change of zoning information.
Zoning information is actually changed when configuration is enabled after the change.
Some setting errors before and/or after zoning change may cause a system fault to
occur.
zone1; zone2
1,0;
1,1
1,4;
1,5
1,0
1,1
1,4
1,5