Hardware installation
Installing the telescopic rail with variable support
3
Figure 5: Fit the left telescopic rail in the PRIMECENTER/DataCenter Rack
Ê Position the left-hand rail (1) in the support bracket with the vertical lug (a)
in the middle square catch.
Ê Press the left rail together until its front end passes behind the front left
support upright (2), then release.
Ê Secure the rail on the front left support upright (3) and the support bracket in
the rack (4) with two (M5) screws each.
Ê Repeat the steps with the right telescopic rail (to be secured to the right
support uprights).
Ê Insert the server (see
Ê Route the cables once the server has been inserted, as described in the
Technical Manual for the rack in question.