Elimination of condensation:
Warning: your device can produce several liters of water per day. You are strongly recommended to guide
the flow to drains.
connect a Ø18 interior pipe (not supplied), to the grooved end piece mounted on the base of the
appliance,
outlet: to the back or on the side:
2.5 Electrical connections
2.5.1 Voltage and protection
the electrical supply to the heat pump must pass via a protection and disconnection device (not supplied)
complying with the standards and regulations in force in the country,
additional protection may be required during installation to guarantee overvoltage category II,
the device is designed for connection to a general power grid with TT and TN.S grounding systems,
electrical protection: circuit‐breaker (curve D) or fuse (Am) (see § 2.5.3 for ratings), and with a 30 mA
differential trip switch (circuit‐breaker or switch) dedicated.
electrical conduits must be secured,
tolerance for voltage variation: ± 6% (during operation),
use cable suitable for outdoor use, type RO2V or equivalent in countries outside of the European
community, and with an outer diameter between 9 and 18 mm,
use the stuffing box to run the supply cable into the device.
2.5.2 Connections
the electrical supply cable must not be exposed to elements that are sharp, hot or represent a crush hazard,
check that all cables are secure and all terminal connections are correct.
Loose terminals may cause the supply terminal board to overheat, and will void the warranty.
The device must be connected to an earth electrode.
Risk of electric shock inside the device.
The device must only be connected by a qualified and experienced technician.
If the power cable is damaged, it must be replaced by a qualified technician.
Single‐phase
phase (L) + neutral (N) + Earth (PE)
2.5.3 Cable cross‐sections
•supply cable cross‐section: cables with a maximum length of 20 metres (calculation base: 5A/mm²), must be
checked and adapted depending on installation conditions.
PFP
Voltage
6M
230V‐50Hz
8M
230V‐50Hz
11M
230V‐50Hz
11T
400V‐50Hz
13M
230V‐50Hz
15M
230V‐50Hz
15T
400V‐50Hz
H03620‐00.B5.EN – 2011/11
Maximum I input
A
9
10
14.5
5
16.1
22
9.4
Three‐phase
phases (L1 + L2 + L3) + neutral (N)
Cable cross‐section
mm²
3 x 2.5
3G2.5
3 x 2.5
3G2.5
3 x 2.5
3G2.5
5 x 2.5
5G2.5
3 x 4
3G4
3 x 6
3G6
5 x 2.5
5G2.5
+ Earth (PE)
Electrical protection
A
16
16
16
10
20
25
10
5