Required Number Of Outlets/Sockets; Table 1.12 Power Distribution Unit (Ac200-240V, 2U, 16 Outlets) Specifications - Fujitsu ETERNUS DX500 S3 Site Planning Manual

Disk storage system
Hide thumbs Also See for ETERNUS DX500 S3:
Table of Contents

Advertisement

Chapter 1
ETERNUS DX Installation
1.7
Outlet/Socket Specifications
Power Distribution Unit (AC200-240V, 2U, 16 Outlets)

Table 1.12 Power Distribution Unit (AC200-240V, 2U, 16 Outlets) Specifications

Outlet
Socket type
(Socket)
IEC60320-C13
1.7.2

Required Number of Outlets/Sockets

The number of power outlets/sockets required to install the ETERNUS DX depends on the number of drive
enclosures and power distribution units.
It is recommended that the power cords of the drive enclosures are connected to the power distribution units
that are installed in the same rack. Secure the necessary number of power outlets within the same rack to
avoid connecting power cords to power outlets in different racks. It may be necessary to purchase additional
power distribution units depending on the installation locations of enclosures.
Without Power Distribution Units
Two power sockets are required for every controller enclosure, 2.5" type drive enclosure, and 3.5" type drive
enclosure.
Four power sockets are required for each high-density drive enclosure.
With Power Distribution Units
Two power sockets are required for each power distribution unit.
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Inlet
Socket type
Plug type
(Socket)
NEMA L6-30P
NEMA L6-30R
30
Copyright 2014 FUJITSU LIMITED
Voltage rating/current
rating
Cable length
4.0m
Rating: 250V 30A
(Normal usage rating:
24A)
P3AM-7712-05ENZ0