Figure 1.13 Breaking Characteristics Of Distribution Board Circuit Protectors - Fujitsu ETERNUS DX500 S3 Site Planning Manual

Disk storage system
Hide thumbs Also See for ETERNUS DX500 S3:
Table of Contents

Advertisement

Chapter 1
ETERNUS DX Installation
1.7
Outlet/Socket Specifications
Breaking Characteristics
The breaking characteristics (*1) of distribution board circuit protectors must be equivalent to or slower than
D (IEC898), which is shown in
*1: Relationship between the size of excess current and operation time

Figure 1.13 Breaking Characteristics of Distribution Board Circuit Protectors

180
120
60
40
20
10
6
4
2
1
40
20
10
6
4
2
1
0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01
1
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Figure
1.13.
B
C
D
~
~
~
1.5 2
3 4
5 6 7 8 10
15 20
Current (ratio for the current rating)
Copyright 2014 FUJITSU LIMITED
30 40 50
80 100
32
P3AM-7712-05ENZ0