Chapter 1
ETERNUS DX Installation
1.1
Installation Specifications
Item
Maximum heat
generation
Maximum
amount of ex-
haust air
Environmental
conditions
Vibration limit
Noise emission
(*3)
*1: A 2U power distribution unit is composed of two 1U power distribution units.
*2: These values are for each drive enclosure when 24 drives are installed in a 2.5" type drive enclosure, 12
drives are installed in a 3.5" type drive enclosure, or 60 drives are installed in a high-density drive en-
closure.
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Controller enclosure
Drive enclosure
2.5" type
(*2)
3.5" type
High-density
type
Controller enclosure
Drive enclosure (*3)
Temperature
Temperature gradient
Humidity
Humidity gradient
Maximum wet bulb temperature
Altitude above sea level
Airborne dust
Gas concentration tolerance level
Oil vapor
Seawater (salt corrosion)
Operating
Not operating
Sound Pressure Level
Sound Power Level
Copyright 2014 FUJITSU LIMITED
ETERNUS DX500 S3
AC 100 – 120V
2,400kJ/h
AC 200 – 240V
2,800kJ/h
AC 100 – 120V
1,600kJ/h
AC 200 – 240V
1,600kJ/h
AC 100 – 120V
1,300kJ/h
AC 200 – 240V
1,300kJ/h
AC 100 – 120V
4,700kJ/h
AC 200 – 240V
4,700kJ/h
3
5.1m
/min
2.5" type
3
4.0m
/min
3.5" type
3
4.0m
/min
High-density
3
12.0m
type
Operating
10 – 40°C
Not operating
0 – 50°C
Shipping
-40 – 60°C
15°C/Hr or less
Operating
20 – 80%RH
Not operating
8 – 80%RH
Shipping
8 – 90%RH
30%/day or less
29°C
0 – 3000m
0.15mg/m
Cl
: 3.4ppb or less, H
2
SO
: 37ppb or less, NH
2
NO
: 52ppb or less, O
2
HCl: 6.6ppb or less, HF: 3.6ppb or less
0.2mg/m
If the ETERNUS DX is installed on the ocean or
premises within 0.5km from the coast, necessary
measures must be taken to prevent salt corro-
sion.
400gal
1,000gal
53dB (A)
7.0B
12
/min
3
or less
S: 7.1ppb or less,
2
: 420ppb or less,
3
: 5ppb or less,
3
3
or less
P3AM-7712-05ENZ0