Making The Lon Connection - Viessmann VITOTRONIC300 Installation And Service Instructions Manual

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Commissioning

Making the LON Connection

The line may be up to ≤ 23 ft. (7 m) long
Legend
A Control unit or Vitocom
B LON cable, 23 ft. (7 m) long
C Terminator
Connection with Viessmann LON cable and coupling
Installation spacing 23 to 69 ft. (7 to 21 m)
Legend
A Control unit or Vitocom
B LON cable, 23 ft. (7 m) long
Max. 3 cables between 2 appliances
C Terminator
D LON coupling
Connection with LON cable, on-site cable and LON
junction box
The line may be up to ≤ 3000 ft. (900 m) (with LON
junction boxes)
Legend
A Control unit or Vitocom
B LON cable, 23 ft. (7 m) long
C Terminator
D LON junction boxes
E On-site cable
F Up to 99 participants
64
≤ 3000 ft.
Vitotronic 300, GW2B Installation and Service
The Viessmann LON system is designed for the
"Line" BUS topology with a terminator at both ends
(accessories). The transfer distances for LON are subject
to the electrical properties of the respective cabling.
For this reason, only use the stated cable types.
Use only one type of cable within the LON.
Observe the cabling requirements for the operation of
the LON interface FTT 10-A (see www.echelon.com).
All Viessmann equipment is connected via RJ45 plugs.
The Viessmann LON system always requires the cores
"1" and "2" and the screen. The cores are
interchangeable. The installation is therefore safe from
pole errors.
Connection with on-site cable and LON plug
≤ 3000 ft.
The line may be up to ≤ 3000 ft. (900 m)
(with LON plug)
Legend
A Control unit or Vitocom
B On-site cable
C Terminator
D LON plug
E Up to 99 participants

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300 gw2b

Table of Contents