Viessmann VITOTRONIC300 Installation And Service Instructions Manual page 103

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Vitotronic 300, GW2B Installation and Service
"General" Group
Coding in the factory set condition
88:0
Temperature displayed in °C (Celsius).
8A:175
Do not adjust.
8F:0
Operation in the standard menu and extended
menu enabled.
Note: The respective code is only activated
when you exit the service level
(see page 65).
90:128
Time constant for calculating adjusted outside
temperature 21.3 h.
91:0
Connection at terminals 1 and 2 in plug aVD
disabled (external heating program changeover)
(see page 55).
93:0
Central fault message during emissions test
function/service display does not affect central
fault.
95:0
Without Vitocom 100 communication
interface.
96:1
With extension for heating circuits 2 and 3
with mixing valve.
(continued)
Possible change
88:1
Temperature displayed in °F (Fahrenheit).
-
-
8F:1
Operation in the standard menu and extended
menu blocked.
8F:2
Operation enabled in the standard menu;
blocked in the extended menu.
90:1
Fast (low values) or slow (high values)
to
matching of the supply temperature, subject
90:199
to the set value when the outside temperature
changes.
1 step
10 min
91:1
Contact affects the following heating circuits:
Heating circuit without mixing valve A1
(heating circuit 1).
91:2
Heating circuit with mixing valve M2
(heating circuit 2).
91:3
Heating circuits without mixing valve A1
(heating circuit 1) and heating circuit with
mixing valve M2 (heating circuit 2).
91:4
Heating circuit with mixing valve M3
(heating circuit 3).
91:5
Heating circuits without mixing valve A1
(heating circuit 1) and heating circuit with
mixing valve M3 (heating circuit 3).
91:6
Heating circuits with mixing valve M2
(heating circuit 2) and M3 (heating circuit 3).
91:7
Heating circuit A1 (heating circuit 1) and
heating circuits with mixing valve M2
(heating circuit 2) and M3 (heating circuit 3).
93:1
Central fault message during emissions test
function/service display does affect central
fault.
95:1
With Vitocom 100 communication interface;
automatic recognition.
96:0
Without extension for heating circuits 2 and 3
with mixing valve.
Code 2
103