Checking Actuator And Sensors - Viessmann VITOTRONIC300 Installation And Service Instructions Manual

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Commissioning
Matching the Coding Addresses to the System Version
Matching coding addresses according to the burner used
Address
Meaning
03:...
Fuel
08:...
Units and tens of the maximum
burner output
09:...
Hundreds of the maximum burner
output
15:...
Modulation range runtime
0A:...
Ratio of output base load to
maximum burner output in percent
05:...
Ratio of partial output at b of the
servomotor runtime to maximum
burner output in percent
Checking Actuators and Sensors
The following actuators (relay outputs) can be controlled subject to the system equipment level:
Display
"All actuators"
OFF
"Base load"
ON
"Burner"
ON
58
Setting
Gas operation: 0 (factory set condition)
Oil operation: 1 (irreversible)
Example: Max. burner output:
225 kW – select: 25
Note: Values up to and including 199 kW can be entered directly.
Example: Max. burner output: 225 kW – select: 2
Calculate runtime (s) of servomotor between base load and max.
burner output
Example: Base load output: 72 kW
Max. burner output: 225 kW
(72 kW: 225 kW) · 100% = 32%
Example: Partial output 171 kW
Max. burner output: 225 kW
(171 kW : 225 kW) · 100% = 76%
Explanation
All actuators have been switched off.
Mod. burner operates at min. output.
Burner stages 1 is switched on.
Vitotronic 300, GW2B Installation and Service
Matching the control unit to a modulating burner
Note: The burner must be fully adjusted. To achieve
a wide modulating range, set the minimum output
as low as possible (take the chimney and flue
system into account).
Testing relays
1. Press OK and
simultaneously for approx. 4 sec.
2. "Actuator test"
(continued)