Viessmann VITOTRONIC300 Installation And Service Instructions Manual page 105

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Vitotronic 300, GW2B Installation and Service
"General" Group
Coding in the factory set condition
9A:0
Connection at terminals 1 and 2 in plug aVD
disabled (external "Mixing valve open")
(see page 48).
9b:70
Set supply temperature for external demand
158°F (70°C).
9C:20
With LON communication module:
Monitoring LON participants.
If there is no response from a participant
after 20 min, the values specified inside the
control unit are used. Only then will a fault
message be issued.
9d:0
Do not adjust
9F:8
Differential temperature 8 K; only in
conjunction with heating circuits with mixing
valve M2 and M3.
(continued)
Possible change
9A:1
No function.
9A:2
External "Mixing valve open"
Heating circuit with mixing valve M2
(heating circuit 2).
9A:3
No function.
9A:4
External "Mixing valve open"
Heating circuit with mixing valve M3
(heating circuit 3).
9A:5
No function.
9A:6
External "Mixing valve open"
Heating circuits with mixing valve M2
(heating circuit 2) and M3 (heating circuit 3).
9A:7
No function.
9b:0
Set value adjustable from 32 to 261°F
to
(0 to 127°C).
9b:127
(limited by boiler specific parameters).
9C:0
No monitoring.
9C:5
Time adjustable from 5 to 60 min.
to
9C:60
-
-
9F:0
Differential temperature adjustable from
to
0 to 40 K.
9F:40
Code 2
105