Viessmann VITOTRONIC300 Installation And Service Instructions Manual page 100

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Code 2
"General" Group
Coding in the factory set condition
4d:1
Connection at plug sL:
Shunt pump.
4E:1
Connection at plug gSA1:
Motor for 3-way mixing valve for return
temperature control.
4F:5
Run-on time, shunt or distribution pump 5 min.
52:0
Without supply temperature sensor for low loss
header.
53:1
With low loss header:
Boiler circuit pump only runs when there
is demand if the burner is operational
(with run-on time).
54:0
Without solar thermal system.
5b:0
Without extension EA1.
5C:0
Function output aBJ at extension EA1:
Central fault message.
5d:0
Function input DE1 at extension EA1:
No function.
100
(continued)
Vitotronic 300, GW2B Installation and Service
Possible change
4d:2
Boiler circuit pump.
4E:2
Motor for 3-way mixing valve, primary store
system.
4F:0
No pump run-on.
4F:1
Run-on time adjustable from 1 to 60 min.
to
4F:60
52:1
With supply temperature sensor for low loss
header; automatic recognition.
53:0
Boiler circuit pump always runs when there
is demand.
54:1
With Vitosolic 100; automatic recognition.
54:2
With Vitosolic 200; automatic recognition.
54:3
With solar control module, type SM1, without
auxiliary function; automatic recognition.
54:4
With solar control module, type SM1, with
auxiliary function, e.g. central heating backup;
automatic recognition.
5b:1
With extension EA1; automatic recognition.
5C:1
Feed pump.
5C:2
No function.
5C:3
Heating circuit pump A1 is switched to low
speed (reduced mode).
5C:4
Heating circuit pump M2 is switched to low
speed (reduced mode).
5C:5
Heating circuit pump M3 is switched to low
speed (reduced mode).
5d:1
Heating program changeover.
5d:2
External demand with minimum set supply
temperature.
Set value selected in coding address "9b".
5d:3
External blocking.
5d:4
External blocking with fault message.
5d:5
Fault message input.
5d:6
Brief operation, DHW recirculation pump
(pushbutton function).
Setting of runtime for DHW recirculation pump
in coding address "12" in the "General" group.