Vitotronic 300, GW2B Installation and Service
"Heating Circuit 1", "Heating Circuit 2", "Heating Circuit 3" Group
Coding in the factory set condition
E1:1
With remote control:
Set day temperature adjustable at the remote
control unit from 50 to 86°F (10 to 30ºC).
E2:50
With remote control:
No display correction of the actual room
temperature.
F1:0
Slab curing function disabled.
F2:8
Time limit for party mode or external heating
program changeover via push button: 8 h
Note: Observe settings of coding addresses
"5d", "5E", "5F" in the "General"
group, as well as "d5" and "d8"
in the "Heating circuit..." group.
F8:-5
Temperature limit for raising reduced mode
23°F (-5ºC); see example on page 83.
Observe the setting of coding address "A3".
F9:-14
Temperature limit for raising the reduced set
room temperature 7°F (-14ºC); see example
on page 83.
FA:20
Raising the set boiler water or supply
temperature by 20% when changing from
operation with reduced room temperature
to operation with standard room temperature.
See example on page 83.
Fb:60
Duration of the set boiler water or supply
temperature rise (see coding address "FA")
60 min. See example on page 83.
*1
Party mode ends automatically in the "Heating and DHW" heating program when the system changes over to
operation with standard room temperature.
Possible change
E1:0
Set day temperature adjustable from 37.5 to
73.5°F (3 to 23ºC).
E1:2
Set day temperature adjustable from 62.5 to
98.5°F (17 to 37ºC).
E2:0
Display correction –5 K
to
to
E2:49
Display correction –0.1 K
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K
F1:1
Only for heating circuits with mixing valve:
to
Slab curing function adjustable in accordance
F1:6
with 6 optional temperature/time profiles
(see page 107).
F1:15
Constant supply temperature 68°F (20°C)
(see page 107).
F2:0
No time limit
*1
.
F2:1
Time limit adjustable from 1 to 12 h
to
F2:12
F8:+10
Temperature limit adjustable from
to
+50 to -76°F (+10 to -60°C).
F8:-60
F8:-61
Function disabled.
F9:+10
Limit for raising the set room temperature to
to
the value selected for standard mode adjustable
F9:-60
from +50 to -76°F (+10 to -60°C).
FA:0
Temperature rise adjustable from 0 to 50%.
to
FA:50
Fb:0
Duration adjustable from 0 to 300 min;
to
1 step
Fb:150
*1
.
2 min.
Code 2
(continued)
*1
.
119