Viessmann VITOTRONIC300 Installation And Service Instructions Manual page 101

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Vitotronic 300, GW2B Installation and Service
"General" Group
Coding in the factory set condition
5E:0
Function input DE2 at extension EA1:
No function.
5F:0
Function input DE3 at extension EA1:
No function.
6C:0
Run-on time for circulation pump, neutralizing
system at output A1 at extension AM1:
None.
6d:0
Run-on time for circulation pump, neutralizing
system at output A2 at extension AM1:
None.
6E:50
No display correction of the outside
temperature.
76:0
Without LON communication module.
77:1
LON participant number.
(continued)
Possible change
5E:1
Heating program changeover.
5E:2
External demand with minimum set supply
temperature.
Set value selected in coding address "9b"
5E:3
External blocking.
5E:4
External blocking with fault message.
5E:5
Fault message input.
5E:6
Brief operation, DHW recirculation pump (push
button function).
Setting of runtime for DHW recirculation pump
in coding address "12" in the "General" group.
5F:1
Heating program changeover.
5F:2
External demand with minimum set supply
temperature.
Selection of set value in coding address "9b"
5F:3
External blocking.
5F:4
External blocking with fault message.
5F:5
Fault message input.
5F:6
Brief operation, DHW recirculation pump (push
button function).
Setting of runtime for DHW recirculation pump
in coding address "12" in the "General" group.
6C:1
Run-on time adjustable from 1 to 255 sec.
to
6C:255
6d:1
Run-on time adjustable from 1 to 255 sec.
to
6d:255
6E:0
Display correction –5 K
to
to
6E:49
Display correction –0.1 K
6E:51
Display correction +0.1 K
to
to
6E:99
Display correction +4.9 K
76:1
With LON communication module (automatic
recognition).
77:2
LON participant number, adjustable from 1 to 99:
to
1 = Boiler control unit
77:99
10 – 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Note: Each number must only be assigned once.
Code 2
101

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300 gw2b

Table of Contents