Connecting Of Combustion Air Device - Viessmann VITOTRONIC300 Installation And Service Instructions Manual

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Installation Sequence
Connection of Combustion Air Device
Legend
A Combustion Air Device Adaptor
B DIN Rail in connection enclosure
50
Vitotronic 300, GW2B Installation and Service
Connection of the Combustion Air Device Adaptor
1. Disconnect power to control and burners.
2. Install Combustion Air Device Adaptor, on DIN Rail
inside connection enclosure (refer to installation
manual of Combustion Air Device Adaptor).
3. Remove jumper between terminals 16 and 17.
4. Make connection as shown in the diagram.
IMPORTANT
Wire BK2 must be connected to terminal 16 and BK3 to
terminal 17 - DO NOT reverse.
For more detail, refer to the combustion air
device Installation Instructions.

Hide quick links: