Boiler" Group - Viessmann VITOTRONIC300 Installation And Service Instructions Manual

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Code 2

"Boiler" Group

Coding
Coding in the factory set condition
02:1
Two -stage burner
03:0
Gas operation.
Factory set condition specified
by the boiler coding card.
04:...
Switching hysteresis, burner:
Factory set condition specified
by the boiler coding card.
05:...
Modulating burner:
Burner curve
Factory set condition specified
by the boiler coding card.
06:87
Maximum limit of the boiler
water temperature set to 189°F
(87°C).
Factory set condition specified
by the boiler coding card.
08:...
Maximum burner output in kW.
Factory set condition defaulted
by boiler coding card.
09:...
Maximum burner output in kW.
Factory set condition defaulted
by boiler coding card.
0A:...
Burner base load in kW.
Factory set condition specified
by the boiler coding card.
106
Vitotronic 300, GW2B Installation and Service
Possible change
02:0
Single stage burner.
02:2
Modulating burner.
03:1
Oil operation (irreversible).
03:2
This occurs automatically, if an incorrect boiler
coding card is inserted or none is present.
04:0
Switching hysteresis 4 K (see page 100).
04:1
Switching hysteresis, heat demand-dependent
(see page 78)
ERB50 function (values from 6 to 12 K).
04:2
ERB80 function (values from 6 to 20 K).
05:0
Linear burner curve.
05:1
Non-linear burner curve
to
(P
: P
T
max
05:99
P
in kW: Partial output at g of the servomotor
T
runtime
P
in kW: Maximum output
max
06:20
Maximum limit adjustable from 68 to 261°F
to
(20 to 127°C).
06:127
Note: Observe the thermostat "
(see page 39).
08:0
Maximum output adjustable from 0 to 199 kW.
to
08:199
09:0
Maximum output adjustable from 0 to 19,900 kW.
TO
1 step
100 kW
08:199
0A:0
Non-linear burner curve
to
(P
:P
)·100%
G
max
0A:100
P
in kW: Base output
G
P
in kW: Maximum output
max
)·100%
" setting
R

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300 gw2b