Vitotronic 300, GW2B Installation and Service
"Heating Circuit 1", "Heating Circuit 2", "Heating Circuit 3" Group
Coding in the factory set condition
b0:0
With remote control:
Heating mode/reduced mode: weather-
compensated.
b2:8
With remote control and for the heating
circuit, operation with room temperature
hook-up must be programmed:
Room influence factor 8.
b5:0
With remote control:
No room temperature dependent heating
circuit pump logic function.
Parameter address b5:...
1
2
3
4
5
6
7
8
Coding in the factory set condition
b6:0
With remote control:
Without quick heat-up/ quick setback.
b7:0
With remote control and for the heating
circuit, operation with room temperature
hook-up must be programmed:
Without start optimization.
b8:10
With remote control and for the heating
circuit, operation with room temperature
hook-up must be programmed:
Heat-up gradient start optimization 10 min/K.
b9:0
With remote control and for the heating
circuit, operation with room temperature
hook-up must be programmed:
Without learning start optimization.
*2
Only change the code for the heating circuit A1 for boilers without lower temperature limit or for the heating circuits
with mixing valve if a remote control is connected to them.
*2
*2
*2
With heating circuit pump logic function:
Heating circuit pump "OFF"
RT
> RT
+ 5 K
actual
set
RT
> RT
+ 4 K
actual
set
RT
> RT
+ 3 K
actual
set
RT
> RT
+ 2 K
actual
set
RT
> RT
+ 1 K
actual
set
RT
> RT
actual
set
RT
> RT
- 1 K
actual
set
RT
> RT
- 2 K
actual
set
*2
*2
*2
*2
Possible change
b0:1
Heating mode: weather compensated
Reduced mode: with room temperature
hook-up
b0:2
Heating mode: with room temperature
hook-up
Reduced mode: weather compensated
b0:3
Heating mode/reduced mode: with room
temperature hook-up
b2:0
Without room influence.
b2:1
Room influence factor adjustable from
to
1 to 64.
b2:64
b5:1
Heating circuit pump logic function,
to
see the following table.
b5:8
Heating circuit pump "ON"
RT
actual
RT
actual
RT
actual
RT
actual
RT
actual
RT
actual
RT
actual
RT
actual
Possible change
b6:1
With quick heat-up/quick setback (see
function description on page 105).
b7:1
With start optimization, max. heat-up time
delay 2 h 30 min.
b7:2
With start optimization, max. heat-up time
delay 15 h 50 min.
b8:11
Heat-up gradient adjustable from 11 to 255
to
min/K.
b8:255
b9:1
With learning start optimization.
Code 2
(continued)
< RT
+ 4 K
set
< RT
+ 3 K
set
< RT
+ 2 K
set
< RT
+ 1 K
set
< RT
set
< RT
- 1 K
set
< RT
- 2 K
set
< RT
- 3 K
set
117