Viessmann VITOTRONIC300 Installation And Service Instructions Manual page 108

Weather-compensated, digital boiler control units for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Code 2
"Boiler" Group
Coding in the factory set condition
1F:0
With flue gas temperature sensor:
Flue gas temperature is not monitored for
service display.
21:0
No service interval (hours run) selected.
23:0
No interval for service.
24:0
No "Service" display.
26:0
Burner fuel consumption (stage 1):
No count if "26:0" and "27:0"
are programmed.
27:0
Burner fuel consumption (stage 1):
No count if "26:0" and "27:0"
are programmed.
28:0
No burner interval ignition.
29:0
Burner fuel consumption (stages 1 and 2);
No count if "29:0" and "2A:0"
are programmed.
2A:0
Burner fuel consumption (stage 2);
no count if "29:0" and "2A:0"
are programmed.
2d:0
Shunt pump "ON" only in case of demand.
108
(continued)
Vitotronic 300, GW2B Installation and Service
Possible change
1F:1
When the flue gas temperature limit
to
is exceeded, "Service" is displayed.
1F:250°C
21:1
The number of hours run before the burner
to
should be serviced is adjustable from 100
21:100
to 10,000 h.
1 step
100 h.
23:1
Interval adjustable from 1 to 24 months.
to
23:24
24:1
"Service" display (the address is
automatically set and must be manually
reset after a service has been carried out).
26:1
Input of 0.1 to 9.9;
to
1 step
0.1 L/h or gallons/h
26:99
Note: Values of coding addresses "26"
and "27" are added together.
27:1
Input of 10 to 1990;
to
1 step
10 L/h or gallons/h
27:199
28:1
Time interval adjustable from 1 to 24 h.
to
The burner is force started for 30 sec. each
28:24
time.
29:1
Input of 0.1 to 9.9;
to
1 step
0.1 L/h or gallons/h
29:99
Note: Values of coding addresses "29"
and "27" are added together.
2A:1
Input of 10 to 1990;
to
1 step
10 L/h or gallons/h
2A:199
2d:1
Shunt pump constantly "ON".

Hide quick links: