Removal Of Compressor(For Rzp100~140D); Removal Of Compressor (For Rzp100~140D) - Daikin SkyAir Super Inverter 70 D Series Service Manual

Split system air conditioners d series;
Table of Contents

Advertisement

SiE25-110
2.7

Removal of Compressor (For RZP100~140D)

Procedure
before disassembling work.
Step
Remove the outside
panels according to the
procedure for removing
outside panels, etc.
1. Removing the front panel
and partition plate
1
Remove the 8 screws
on the front panel (1) to
dismount it.
2
Remove the 6 screws
on the stop valve
mounting plate to
dismount it.
3
Remove the 8 screws
on the partition plate to
dismount it.
2. Removing the sound
insulating material
1
Remove the
compressor terminal
cover and disconnect
the lead wire.
2
Remove the 1 string to
dismount the sound
insulating materials A
and B.
3
Remove the adhesive
tape to draw the
insulating material D
out.
4
Remove the 2 strings to
draw the insulating
material C.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
Procedure
RZP71~140D
Points
Make sure that there is no
refrigerant in the unit before
disassembling.
Warning
If the refrigerant gas leaks
during the service work,
ventilate the area. (When the
refrigerant gas contacts
flames, toxic gases may be
generated.)
221