2.6

Removal of Compressor (For RZP71D)

Procedure
before disassembling work.
Step
Remove the front panel
(2) and piping cover front
panel according to the
procedure for removing
outside panels.
1. Removing the sound
insulation cover
1
Remove the 6 screws
on the stop valve
mounting plate to
dismount it.
2
Remove the string
securing the sound
insulating material to
draw it out.
3
Remove the
compressor terminal
cover and disconnect
the lead wire.
2. Removing the
compressor
1
Remove the nut from
the compressor
mounting bolt (1
location).
2
Disconnect the suction
pipe (A) and discharge
pipe (B) at the brazed
sections.
3
Lift up the compressor
to clear the mounting
bolt to remove the
compressor.
220
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
Procedure
SiE25-110
Points
Make sure that there is no
refrigerant in the unit before
disassembling.
Warning
If the refrigerant gas leaks
during the service work,
ventilate the area. (When the
refrigerant gas contacts
flames, toxic gases may be
generated.)
Removal Procedure