Field Piping - Daikin SkyAir Super Inverter 70 D Series Service Manual

Split system air conditioners d series;
Table of Contents

Advertisement

SiE25-110
1.2

Field Piping

This unit requires additional charging of refrigerant according to the length of pipe connected at the site.
When the entire refrigerant pipe length is within 30 meters, the additional changing is not needed.
Take the following steps for proper charging.
When connected to indoor units
One way length of pipe (L)
(1) Additional charging of refrigerant
Select the appropriate refrigerant charging amout from Table 2, 3 and charge the refrigerant. Fill out the
notice plate attached in the rear of the front plate (2) for future servicing.
• Pair-type
Table 1 Additional charging refrigerant amount
Pipe excess length over 30 meters
71, 100, 125, 140 type
Simultaneous operation multi-type
• Find the entire pipe length by totaling that of each pipe in the order of the main pipe (L1), and branched
pipes (L2), (L3) calculate the excess length going over 30 meters, then select from Table 3 the amount of
refrigerant corresponding to the excess length.
The total value is the amount required for additional charging.
Table 2 Additional charging amount
Pipe excess length over 30 meters
Liquid pipe
(2) Complete charging of the refrigerant
When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the
amount mentioned in the nameplate, and when the pipe length exceeds 30 meters, the charging amount
mentioned in the nameplate and that required for additional charging are to be totaled as the net charging
amount.
*Vacuum drying when refilling the refrigerant will not be sufficient if done only at the shut-off valve service
port (gas and liquid sides), so it should be done from a service port set up on the pipe leading from the out-
door unit 4-path switch valve to the heat exchanger.
Field Piping and Wiring
When connected to two indoor units
Branched pipe
(L2)
Main pipe (L1)
One-way length of pipe (L) : L1+L2+L3
10m or less
9.5
0.4
Branched pipe (L3)
20m or less
0.8
20m or less
30m or less
0.8
1.2
Field Piping and Wiring
(unit: kg)
40m or less
1.6
(unit: kg)
40m or less
1.6
(S2535)
35