Removal Of Solenoid Valve And Motorized Valve (For Rzp71D); Removal Of Solenoid Valve And Motorized Valve - Daikin SkyAir Super Inverter 70 D Series Service Manual

Split system air conditioners d series;
Table of Contents

Advertisement

RZP71~140D
2.9
Removal of Solenoid Valve and Motorized Valve (For
RZP71D)
Procedure
before disassembling work.
Step
Remove the front panel
(2) and piping cover front
panel according to the
procedure for removing
outside panels, etc.
Remove the stop valve
mounting plate according
to the procedure for
removing the compressor.
Remove the 7 screws
1
on the front panel (1) to
dismount it.
2
Disconnect the
connector of reactor.
3
Disconnect the internal
wiring from the clamp
material attached to the
partition plate.
4
Remove the 5 screws
on the partition plate to
dismount it.
1. Removing the solenoid
valve
1
Remove the 1 screw to
disconnect the solenoid
valve coil.
2
Disconnect the solenoid
valves at each 2 brazed
sections.
2. Removing the motorized
valve
1
Pull the motorized valve
coil out upward.
2
Disconnect the
motorized valve at the 2
brazed sections.
224
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
Procedure
SiE25-110
Points
Make sure that there is no
refrigerant in the unit before
disassembling.
Warning
If the refrigerant gas leaks
during the service work,
ventilate the area. (When the
refrigerant gas contacts
flames, toxic gases may be
generated.)
Installing solenoid valve coil
Install the coil by using one
screw.
Installing motorized valve
coil
Insert the coil so that the
holder can fit into the piping.
Check that the coil cannot
be removed when lifting it.
Removal Procedure