Troubleshooting by Remote Controller Display / LED Display
6.12 Malfunction of Remote Controller Air Thermistor
CJ
Remote
Controller
Display
Applicable
FHYCP, FHYP, FUYP, FAYP
Models
Method of
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction
Malfunction detection is carried out by temperature detected by remote controller thermistor.
Detection
Malfunction
When the remote controller thermistor becomes disconnected or shorted while the unit is
running.
Decision
Conditions
Supposed
Causes
Troubleshooting
146
Failure of sensor itself
Broken wire
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn the power supply
off once and then
back on
Is CJ
displayed on the
YES
remote
controller?
NO
SiE25-110
Replace remote controller.
Could be outside cause
(noise,etc.) other than
malfunction
(S1168)
Troubleshooting