CONNECTION FOR OPTIONS

The installation and cabling of the options must be performed a qualified
service person.

9.4.1 Remote Signaling Box (RSB)

The optional Remote Signaling Box allows monitoring of the operation of the UPS, using the potential
free contacts fitted on the "P4 - Customer Interface Board" of the UPS.
It can be used by simply putting the box on a desktop or on a wall or, removing the box, it can be
surface mounted.
The remote panel contains an internal buzzer and the following status indicators:
Mimic diagram
with LED's indicating the operation of Rectifier and Inverter, and the power
source supplying the critical Load.
Alarm
(LED light and audible alarm) indicating a critical situation on the UPS.
Stop
indicating the UPS is preparing to shut down in a short time.
Mute
push button to reset the buzzer.
Test
push button checks all the LED's and the buzzer of the remote panel.
The cable connecting the RSB to the UPS cabinet must be min. 16 wires / 0.25mm
The plug B is included in the delivery of the option RSB (cable connecting UPS with RSB not included).
Maximal admitted length: 985 ft (300 m).
It must be wired at one end with a D - female plug- 25 pin (J2 – P4 Customer Interface Board).
The alarms on free potential contacts can be connected on terminals X1
instead J2 (see correlation X1 – J2 in chapter 8.1).
pink
XA
red
grey
TERMINALS
blue
BLOCK
25
24
23
22
21 white
brown
20
19
green
18
yellow
17
16
black
15
violet
14
13
12
11
10
9
grey/pink
8
blue/red
7
6
white/green
5
brown/green
4
white/yellow
3
yellow/brown
2
1
P.S.: The above mentioned colors are
suitables only for XY standard cable
A
Terminals X3, X4 and X15 fitted inside the Remote Signaling Box.
B
Plug J2 (sub D - male - 25 pin) must be connected to the connector J2 (sub D - female-
25 pin) located on "P4 - Customer Interface Board".
XA
Terminals block XA for 24 VDC / 1A supply Remote Signaling Box.
If the remote signal panel is plugged on connector J2, the terminal blocks X1
cannot be used to drive an external alarms monitoring device, because it is
supplied by the internal UPS low voltage power supply.
OPM_SGS_USM_10K_40K_0US_V010.doc
A
REMOTE
SIGNALLING
BOX
IM6544
24V
1
X15
GND
2
31
UTILITY FAILURE
32
33
34
37
38
40
42
X4
43
LOAD ON INVERTER
44
P4 - IM0005
49
Customer Interface
LOAD ON MAINS
50
55
56
16
COMMON ALLARM
17
19
X3
AUX. BUZZER
20
22
STOP OPERATION
23
Fig. 8.4.1-1 Remote Signaling Box connection
84/88
2
.
Pink + Red
1
XA
XA
TERMINALS BLOCK
2
Grey + Blue
1
J2
B
2
PLUG
3
SUB D - MALE
4
J2
1
2
3
4
A
Stop
Alarm
g
Mute
Test
GE Digital Energy
8 1/2" in
216mm
Operating Manual SG Series 10, 20, 30 & 40 kVA
GE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents