ICON I100 INSTALLATION INSTRUCTIONS
2. Chase Top
Construct a chase of desired materials maintaining a
minimum 2” air space around the chimney.

3. Termination Cap

Install the chimney sections up through the chase
enclosure. When using a TR11 round termination
cap, the uppermost top section of pipe must extend
6” above the top of the chase collar to allow
installation of the storm collar and termination cap.
See Figure 40.
For installations utilizing a TR11T telescoping
round termination cap, the uppermost chimney
section must be below the top of the chase top,
but not more than 14½” below the top of the chase
top flashing collar. See Figure 41.
For installations utilizing an ST1175 square
termination cap the last chimney section must not
be more than 4½” below the chase top. See
Figure 42.
Attach the chase top to the top of the chase.
Install the termination cap, following the
instructions provided with it.
Figure 41 - Installing a TR11T Round Telescoping Termina-
tion Cap
12/03
Figure 40 - Installing a TR11 Round Termination Cap
Figure 42 - Installing an ST1175 Square Termination Cap
WARNING!
WARNING!
35144 Rev E