Woodburning fireplace
Table of Contents

Advertisement

2. Frame the Fireplace
The I100 fireplace will fit a framed opening of 61
30
/
”.
3
8
Figure 5 shows a typical framing (using 2 x 4 lumber) of the fireplace, assuming combustible materials are used. All
required clearances to combustibles around the fireplace must be adhered to. Any framing across the top of the
fireplace must be above the top of the standoffs.
Note:
side and 1½” above the top. This should be allowed for when applying facing to the front of the fireplace.
3. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum of 24” from the fireplace opening. See Figure 6. If you
are using a decorative surround constructed of combustible material, it must be located within the shaded area
defined in Figure 6. Short stub walls are also acceptable if they are contained within the shaded area.
10
Figure 5 - Framing the Fireplace
The frame of the AED door overlaps the front of the fireplace beyond the opening by ¾” on each
ICON I100 INSTALLATION INSTRUCTIONS
/
” wide x 61” tall. The finished cavity depth must be no less than
5
8
WARNING!
Figure 6 - Sidewalls and Surrounds
35144 Rev E
CLEARANCES!
12/03