Function list (Extended function
parameters)
Name
If the difference between speed command value and speed exceeds the setting of the
870 Speed deviation level
speed deviation level (Pr. 870) for longer than the setting of the speed deviation time
(Pr. 871), speed deviation excessive "E.OSD" is displayed and the motor stops.
0 to 1500r/min, 9999
871 Speed deviation time
0 to 100s
873 Speed restriction
0 to 3600r/min
Set the load level of the motor at which OLT alarm.
874 OLT level setting
0 to 200%
You can classify faults into a minor fault and major faults according to the alarms, and
make setting to select between immediate output shutoff and output shutoff after
deceleration to stop.
875 Fault definition
0: Immediate output shutoff
1: Output shutoff after deceleration to stop (Immediate output shutoff other than OHT
When using the motor provided with PLG, you can input the contact signal of a thermal
Thermal relay
relay etc. to terminal OH to provide motor protection against overheat.
876
protector input
0: None
1: Thermal relay input available
Select speed feed forward control (which improves the motor trackability in response to
Speed feed forward
a speed command change (during acceleration/deceleration)) or model adaptive speed
control/model
877
control (that can adjust speed trackability and motor disturbance torque response level
adaptive speed
individually). (0: No selection, 1: Speed feed forward control, 2: model adaptive speed
control selection
control)
Set the primary delay filter for the speed feed forward result calculated using the speed
Speed feed forward
878
command and load inertia ratio.
filter
0 to 1s
Speed feed forward
Restricts the maximum value of the speed feed forward torque.
879
torque restriction
0 to 400%
880 Load inertia ratio
Set the load inertia ratio. Inertia ratio found by easy gain turning. 0, 1 to 200 times
Speed feed forward
Set the feed forward calculation result as a gain.
881
gain
0 to 100%
Maintenance output
890
Signal outputs and functions for indicating that the cumulative energization time of the
setting time
inverter has reached a given time. (Used for warning that the capacitor life is reached,
Maintenance output
for example.)
891
timer
Pr.890:0 to 9998, 9999: No setting
Pr.891:0 to 9998
Maintenance output
892
Pr.892:0
signal clear
DA1 terminal
900
For calibration of external meter
calibration
DA2 terminal
901
For calibration of external meter
calibration
You can set the magnitude of the output in response to the speed setting signal (0-
Speed setting No.2
902
10VDC) as desired.
bias
0 to 10V, 0 to 3600r/min
You can set the magnitude of the output in response to the speed setting signal (0-
Speed setting No.2
903
10VDC) as desired.
gain
0 to 10V, 0 to 3600r/min
You can set the magnitude of the output in response to the torque setting signal
Torque command
904
(0±10VDC) as desired.
No.3 bias
0 to 10V, 0 to 400%
You can set the magnitude of the output in response to the torque setting signal
Torque command
905
(0±10VDC) as desired.
No.3 gain
0 to 10V, 0 to 400%
You can set the magnitude of the output in response to the No. 1 terminal analog
No. 1 terminal bias
917
setting signal (0±10VDC) as desired.
(Speed)
0 to 10V, 0 to 3600r/min
You can set the magnitude of the output in response to the No. 1 terminal analog
No. 1 terminal gain
918
setting signal (0±10VDC) as desired.
(Speed)
0 to 10V, 0 to 3600r/min
You can set the magnitude of output (torque/magnetic flux) in responce to the No.1
No. 1 terminal bias
919
terminal analog set signal (DC0 ±10V) as desired.
(torque/magnetic flux)
0 to 10V, 0 to 400%
You can set the magnitude of output (torque/magnetic flux) in responce to the No.1
No. 1 terminal gain
920
terminal analog set signal (DC0 ±10V) as desired.
(torque/magnetic flux)
0 to 10V, 0 to 400%
You can control the "beep" sound produced when any key of the parameter unit is
pressed.
990 Buzzer control
0: Without sound
1: With sound
991 Parameter for the option (FR-PU04V)
Outline
CAUTION
Use this function when a difference in speed will constitute a hindrance. It is
independent of torque control.
and THM)
Factory
Setting
600r/min
150%
150%
0V, 0r/
1 50 0r/m in
0V, 0%
150%
0r/min
1 50 0r/m in
0V, 0%
150%
69
At-a-glance Guide to Func-
tions
" " " " : Usable function
×: Unusable function
Cus-
* : Functions that can be used
tomer
for param eter-set position con-
Set-
trol
ting
Vector Control
Speed
Torque
Position
control
control
" " " "
×
9999
" " " "
×
12s
×
" " " "
" " " "
×
" " " "
" " " "
0
" " " "
" " " "
1
" " " "
×
0
" " " "
×
0s
" " " "
×
" " " "
×
7
" " " "
×
0%
" " " "
" " " "
9999
" " " "
" " " "
0
" " " "
" " " "
0
" " " "
" " " "
" " " "
" " " "
" " " "
" " " "
min
1 0V,
" " " "
" " " "
" " " "
" " " "
10V,
" " " "
" " " "
0V,
" " " "
" " " "
1 0V,
" " " "
" " " "
" " " "
" " " "
10V,
" " " "
" " " "
" " " "
" " " "
1