Mitsubishi Electric FR-V520-1.5K to 55K Instruction Manual page 60

Vector inverter
Hide thumbs Also See for FR-V520-1.5K to 55K:
Table of Contents

Advertisement

Name
You can select the monitor output DA1 data.
1: Speed
2: Output current
3: Output voltage
5: Preset speed
6: Output frequency
7: Motor torque
8: Converter output voltage
9: Regenerative brake duty
DA1 terminal function
54
10: Electronic thermal relay load factor
selection
11: Output current peak value
12: Converter output voltage peak value
17: Load meter
18: Motor exciting current
21: Reference output
32: Torque command
33: Torque current command
34: Motor output
36: Torque monitor (driving/regenerative polarity switching)
Speed monitoring
You can set the reference value of speed monitoring.
55
0 to 3600r/min
reference
Current monitoring
You can set the reference value of current monitoring.
56
reference
0 to 500A
When power is restored after an instantaneous power failure, you can start the inverter
57 Restart coasting time
without stopping the motor (in a coasting status). When this time (Pr. 57) elapses after
power was restored, the inverter begins to restart.
When you set "9999", the inverter will not restart. Generally, you may set "0", but you
can adjust the time (0, 0.1 to 5s, 9999) according to the load magnitude.
58 Restart cushion time
When the restart coasting time (Pr. 57) elapses, the output voltage is risen gradually.
Set this cushion time (Pr. 58) (0 to 60s).
Normally, you can perform operation with the factory settings, but you can adjust them
according to the load magnitude. Pr. 58 is valid only during V/F control.
You can make remote setting of the speed when the operation panel is located away
from the control box.
0: None
Remote setting
59
1: With remote setting function, with frequency setting storage function
function selection
2: With remote setting function, without frequency setting storage function
3: With remote setting function, without frequency setting storage function
(Turning STF/STR off clears remote setting)
Set when using the brake sequence control.
0: Normal operation mode
Intelligent mode
7: Brake sequence mode
60
selection
(With mechanical brake opening completion signal input)
8: Brake sequence mode
(Without mechanical brake opening completion signal input)
You can select alarms for a retry to be made when the protective function is activated.
0:E.OC1 to 3, E.OV1 to 3, E.THM, E.THT, E.IPF, E.UVT, E.BF, E.GF, E.OHT, E.OLT,
E.OPT, E.OP1 to 3, E.PE, E.OS, E.OSD, E.OD, E.MB1 to 7
1:E.OC1 to 3
65 Retry selection
2:E.OV1 to 3
3:E.OC1 to 3, E.OV1 to 3
4:E.OC1 to 3, E.OV1 to 3, E.IPF, E.UVT, E.BF, E.GF, E.OLT, E.OPT, E.OP1 to 3, E.PE,
E.OS, E.OSD, E.OD, E. MB1 to 7
5:E.OC1, E.OC3
You can set the number of retries to be made when the protective function is activated.
Number of retries at
0: Retry not made.
67
alarm occurrence
1 to 10: Without alarm output during retry operation
101 to 110: With alarm output during retry operation
You can set the waiting time from activation of the protective function to a retry.
68 Retry waiting time
0 to 10s
You can display the cumulative number of successful restarts made by retries when the
Retry count display
69
protective function was activated.
erasure
0
Special regenerative
Set to increase the regenerative brake duty when the FR-ABR option is used.
70
brake duty
0 to 15%(1.5K or less), 0 to 30%(2.2K or more)
Function list (Extended function
Outline
56
parameters)
At-a-glance Guide to Func-
tions
" " " " : Usable function
×: Unusable function
Cus-
* : Functions that can be used
Factory
tomer
for param eter-set position con-
Setting
Set-
trol
ting
Vector Control
Speed
Torque
control
control
" " " "
" " " "
1
" " " "
" " " "
1 50 0r/m in
Rated
inverter
" " " "
" " " "
output
current
" " " "
" " " "
9999
×
×
1.0s
" " " "
" " " "
0
" " " "
×
0
" " " "
" " " "
0
" " " "
" " " "
0
" " " "
" " " "
1s
" " " "
" " " "
0
" " " "
" " " "
0%
Position
control
" " " "
" " " "
" " " "
×
×
×
×
×
×
×
×
" " " "
5