Basic operation (Speed setting, run,
speed meter adjustment)
3.2.2
Adjustment (calibration) of speed meter (meter)
Changing example
POINT
• Pr. 900 "DA1 terminal calibration" can be read by setting "1" (extended function parameter enable) in
Pr. 160 "extended function selection".
• Set Pr. 900 "DA1 terminal calibration".
• Set any of "1 to 3, 5 to 12, 17, 18, 21, 32 to 34 and 36" in Pr. 54 "DA1 terminal function selection" to
output a signal to the terminal DA1. (Refer to page 56)
Press
to operate the inverter. (It is not necessary to
1.
FWD
connect a motor.)
2.
Press
to select the parameter setting mode.
MODE
Display the present operation speed by pressing
3.
read Pr. 900.
4.
Press
or
to adjust the meter pointer to
a predetermined position. (Depending on the setting,
it may take some time until the pointer moves.)
REMARKS
1. Pressing
to start reverse rotation operation will move the meter pointer
REV
reversely (in the negative direction).
2. The terminal DA1 output will also keep displaying the monitor when the
inverter stops due to an alarm.
5.
Press
for about 1.5s.
SET
This completes the setting.
STOP
Press
to stop the inverter.
6.
RESET
CAUTION
1. When the speed meter is connected across terminals DA1-5 to monitor the speed, the output of ter-
minal DA1 is saturated if the maximum output speed reaches or exceeds 1500r/min, with the factory
setting unchanged. Hence, the setting of Pr. 55 "speed monitoring reference" must be changed to the
maximum output speed. (Refer to page 56.)
2. Terminal DA2 can be adjusted in Pr. 901
3. For operation from the parameter unit (FR-PU04V), refer to the instruction manual of the FR-PU04V.
REMARKS
• For monitor display changes by
• Calibration can be made also during external operation.
At the preset speed of 1500r/min, make adjustment so that the meter (analog meter)
deflects to full-scale. Calibrate the DA1 terminal (±10V).(in PU operation mode)