Mitsubishi Electric FR-V520-1.5K to 55K Instruction Manual page 19

Vector inverter
Hide thumbs Also See for FR-V520-1.5K to 55K:
Table of Contents

Advertisement

Connection diagram, PLG cable, PU
connector
Terminal
Type
Terminal Name
Symbol
A, B, C
Alarm output
DO1 to
Digital output terminals
DO3
1 to 3
Open collector output
SE
common
DA1
Analog signal output
DA2
Analog signal output
Analog signal output
5
common
PU connector
* Not output during inverter reset.
REMARKS
For the input terminal function switchover timing, refer to page 42.
(2) Control circuit terminal layout
Terminal screw size : M3.5
Tightening torque
: 1.2N·m
When connecting three or more control cables
to the No. 5 terminal, connect the accessory
No. 5 terminal dedicated L-shaped jumper to
the No. 5 terminal.
In this case no cable should be connected to
the screw in the
part.
(3) Wiring instructions
1)
Terminals 5, SD and SE are common to the I/O signals and isolated from each other. These common terminals
must not be connected to each other nor earthed (grounded).
2)
Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main
and power circuits (including the 200V relay sequence circuit).
3)
Since the control circuit input signals are micro currents, use two parallel micro signal contacts or a twin con-
tact to prevent a contact fault.
4)
It is recommended to use the cables of 0.75mm
cable gauge used is 1.25mm
cables are run improperly, resulting in an operation panel or parameter unit contact fault.
5)
The maximum wiring length should be 30m.
1 contact output indicating that the output has been stopped by the inverter
protective function
230VAC 0.3A, 30VDC 0.3A. Alarm: discontinuity across B-C (continuity across A-C),
Normal: continuity across B-C (discontinuity across A-C).
The terminal function varies with the output terminal function selection (Pr. 195)
setting.
Refer to page 61 for details.
Permissible load 24VDC 0.1A
The terminal functions vary with the output terminal function selection (Pr. 190 to Pr.
192) settings. Refer to page 61 for details.
Common terminal for terminals DO1, DO2 and DO3. Isolated from terminals SD and
5.
One selected from the monitoring items,
such as the speed, is output.
The output signal is proportional to the
magnitude of the corresponding monitoring
item.
Common terminal for DA1 and DA2.
Isolated from terminals SD and SE.
Do not earth(ground).
W ith the P U connector, com m unication can be m ade through R S -485.
• Conforming standard : EIA Standard RS-485
• Transmission format
• Communication speed : Maximum 19200bps
• Overall length
A
B
10E
3
5
5
2
gauge for connection to the control circuit terminals. If the
2
or more, the front cover may be lifted when there are many cables running or the
15
Description
Factory setting of output item:
Speed monitoring, output signal 0 to
*
±10VDC, permissible load current 1mA
Factory setting of output item:
Torque monitoring, output signal 0 to
10VDC, permissible load current 1mA
: Multidrop link system
: 500m
C
DO1 DO2 DI4
DI3
DI2
2
DA1
DO3
SE
PZ PZR PG RES
DA2
1
PA PAR PB PBR SD
Jumper
DI1
STR
STF
PC
SD
OH