O Peration; General; Control Panel Front; Factory Tests - Harsco Industrial P-K SONIC SC-3000 Installation & Owner's Manual

Natural gas/propane/dual fuel gas fired boiler
Hide thumbs Also See for P-K SONIC SC-3000:
Table of Contents

Advertisement

To adjust high fire:
Required Tools: Flat head screwdriver and Combustion
analyzer
Start the boiler and observe proper operating parameters for
the system. Set boiler to the "
BNR ON TEST HI
above, to achieve maximum firing rate of the boiler. Check
combustion readings using the combustion analyzer. If
combustion readings are not in accordance with Table 3.11.2,
adjust as follows: Open the front panel of the boiler. Locate
the automatic gas valve. Turn the orifice adjusting screw,
located on the downstream side of the valve, in the direction
indicated on the sticker to increase or decrease the gas flow.
Increasing the gas flow decreases the combustion exhaust
, while decreasing the gas flow increases the combustion
O
2
exhaust
. There will be a slight time delay between the
O
2
adjustment and the response of the
CO
/O
2
2
instrument. Adjust the settings in small increments and allow
the combustion readings to stabilize before readjusting.
When desired adjustments are complete, check and adjust
low fire if necessary.
To adjust low fire:
Required Tools: 2.5 mm hex wrench and Combustion
analyzer
Start the boiler and observe proper operating parameters
for the system. Set boiler to the "
BNR ON TEST LOW
described above, to achieve minimum firing rate of the
boiler. Check combustion readings using the combustion
analyzer. If combustion readings are not in accordance with
Table 3.11.2, adjust as follows: Open the front panel of the
boiler. Locate the automatic gas valve. Turn the offset screw,
located in the bottom center of the side of the valve, in the
direction indicated on the label to increase or decrease the
gas. Increasing the gas decreases the
, while decreasing
O
2
the gas increases the
. There will be a slight time delay
O
2
between the adjustment and the response of the
measuring instrument. Adjust the settings in small increments
and allow the combustion readings to stabilize before
readjusting. When desired adjustments are complete, check
and adjust hi fire if necessary.
3.11.3 Checking Flame signal
Using the control panel, enter the information mode and scroll down view the flame signal. This shows μA when
the boiler is firing and shows 0μA when the boiler is not firing. 7-8μA is a strong flame signal.
26
Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351
", as described
measuring
" as
CO
/O
2
2
Gas Fired Boiler
4 o
peraTIon
4.1 g
eneral

4.1.1 Control Panel Front

Become familiar with the
basic operation of the boiler.
The interior of the front door
shows the boiler Operating
Instructions.

4.1.2 Factory tests

Safe lighting and other
performance criteria were met
with the gas manifold and
control assembly provided
on this boiler when the boiler
underwent factory tests
specified in
ANSI Z21.13/CSA
, latest edition. (See "Factory
4.9
Firetest" label.)
4.2 n
l
orMal
IghTIng and

4.2.1 lighting Procedures

1. Make sure the system is filled with water and water is circulating in the system.
Turn on electrical supply and open the gas supply valves to the boiler.
2. Turn the on/off switch to the on position. If an error is indicated, see Section
5.5 of this manual to troubleshoot the problem and take the necessary corrective
action before proceeding.
3. Set the desired high temperature limit and operating temperature. The
controller will now complete the automatic firing sequence.

4.2.2 Normal shut Down Procedures

1. Close all manual gas valves.
2. Turn off electric power.
4.3 e
MergenCy
In case of emergency, shut off gas at a valve external to the boiler. See
diagram at right for valve locations.
Figure 3.11.2
4.4 T
b
ypICal
oIler
model
Input Rating
Number
(Btu/hr)
SC-3000
3,000,000
SC-4000
4,000,000
Table 4.4
Figure 4.1.1
s
-d
p
huT
oWn
roCedures
s
o
huT
ff
o
C
peraTIng
ondITIons
Voltage
total
Gas Flow Rate (CFh)
(three phase)
Amperage
Natural
lP Gas
Gas
(2500 Btu/ft^3)
(1030 Btu/ft^3)
208-240
Less than 20
1200
2,880,000
2913
440-480
Less than 20
208-240
Less than 20
3689
1520
3,840,000
440-480
Less than 20
Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351
Gas Fired Boiler
!
WARNING
Do not use this boiler if any part
has been under water. Immediately
call a qualified service technician
to inspect the boiler and to replace
any part of the control system and
any gas control which has been
under water.
!
WARNING
If overheating occurs or the gas
supply fails to shut off, do not turn
off or disconnect the electrical
supply to the pump. Instead, shut
off the gas supply at a location
external to the boiler.
n
!
oTICe
The heat exchanger is constructed
and stamped for 160 psig
maximum operating pressure and
210ºF maximum temperature.
Output
Capacity
(Btu/hr)
Figure 4.3
27