Maintenance/Troubleshooting
Authorised electrician
Status
Display
FS
29
Ground fault
Check fuse
FS
30
Fault
transformer fault
FS
31
RCD module error
FS
32
Fault
Self-test
FS
33
Fault
DC feed-in
FS
34
Communication
error
FS
35
Protection
shutdown SW
FS
36
Protection
shutdown HW
FS
38
Error
PV overvoltage
FS
41
Line failure:
undervoltage L1
FS
42
Line failure:
overvoltage L1
FS
43
Line failure:
undervoltage L2
Table 7:
Operating statuses and fault messages on the display
Operating Instructions for Powador 2002-6002_EN
Explanation
!
A ground fault was detected at the PV
generator.
The current and voltage measure-
ments in the inverter are not plausible.
An fault has occurred in the AC/
DC-sensitive residual current device.
The internal grid separation relay test
has failed.
The DC feed-in has exceeded the
permitted value. This DC feed-in can
be adopted from the grid onto the
inverter so that no fault occurs.
A communication error has occurred in
the internal data transmission.
Protective shutdown of the software
(AC overvoltage, AC overcurrent, DC
link overvoltage, DC overvoltage).
Protective shutdown of the
hardware (AC overvoltage, AC overcur-
rent, DC link overvoltage).
The voltage of the DC generator is too
high. The PV generator is confi gured
incorrectly.
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
The voltage of a grid phase is too high,
the grid cannot be fed into.
The phase experiencing failure is dis-
played.
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Action
By
 Notify your
authorised elec-
trician.
-
 Notify your
authorised elec-
trician if the fault
occurs several
times.
 Notify your
authorised elec-
trician if the fault
occurs several
times.
 Notify your
authorised elec-
trician.
 Check the data
cable.
Not a fault
Grid-related
shutdown,
the grid connects
again automatically.
Not a fault
Grid-related shut-
down, the grid con-
nects again automat-
ically.
 Notify your
authorised elec-
trician.
 Notify your
authorised elec-
trician.
 Notify your
authorised elec-
trician.
 Notify your
authorised elec-
trician.
E
-