Description
3.2.7.2
Night start button
The unit switches off in the evening as nightfall approaches. At this point, nothing is shown on the display. In order
to retrieve the values from the current day (daily yield, daily hours of operation and max. feed-in power) after the
display switches off , the unit can also be activated during the night by pressing the night start-up button on the
underside of the inverter.
Figure 6:
Night-start interface on the inverter
3.2.8
Interfaces
The inverter has the following interfaces for communication and remote monitoring:
RS232 port
RS485 interface
S0 interface
You confi gure the interfaces in the Settings mode (see section 8.3 on page 36).
3.2.8.1
RS232 port
Use this monitoring option if you wish to manage system operating data directly on a computer. The data can be
processed with standard spreadsheet programs.
The inverter and computer are connected with a serial 1:1 interface cable.
The cable length should not exceed 20 metres.
The data from the inverter is sent unidirectionally as pure ASCII text via the serial interface. The data is not checked
for errors.
The RS232 interface has the following parameters:
Baud rate
Data bits
9600 baud
8
The table below shows an example of a few lines of data transmitted over the RS232 interface.
Column 1
2
3
00.00.0000 00:05:30
00.00.0000 00:05:40
00.00.0000 00:05:50
00.00.0000 00:06:00
00.00.0000 00:06:10
00.00.0000 00:06:20
00.00.0000 00:06:30
00.00.0000 00:06:40
Table 1:
Excerpt from the RS232 interface transmission log
Key
Column
Meaning
1
Placeholder
2
Daily running time
3
Operating status (see section 8.1 on page 13)
4
Generator voltage in V
5
Generator current in A
Operating Instructions for Powador 2002-6002_EN
Parity
Stop bits
None
1
4
5
6
7
3 363.8
0.37
134
226.1
3 366.0
0.39
142
226.1
3 359.5
0.41
147
226.1
3 369.8
0.42
155
226.1
3 377.0
0.43
162
226.1
3 373.6
0.45
168
226.1
3 364.0
0.48
174
226.1
3 364.3
0.49
178
226.1
Protocol
None
8
9
10
0.53
103
23
0.53
112
23
0.53
116
23
0.58
118
23
0.63
131
23
0.63
133
23
0.68
146
23
0.68
146
23
Column
Meaning
6
Generator power in W
7
Line voltage in V
8
Line current, feed-in current in A
9
Power fed into the grid in W
10
Temperature of the unit in °C
Page 13