Installing the inverter
Authorised electrician
Recommended conductor cross-sections and fuse protection of NYM cables for fi xed wiring according to
VDE 0100 part 430
For cable lengths up to 20 m, use the conductor cross-sections named in table 6. Longer cable lengths require larger
conductor cross-sections.
Model
Powador 2002
Powador 3002
Powador 4202
Powador 5002
Powador 6002
Table 4:
Recommended conductor cross-sections and fuse protection of NYM cables
NOTE
When the line resistance is high (i.e. long grid-side cables), the voltage at the grid terminals of the
inverter will increase during feed-in to the grid. The inverter monitors this voltage. If it exceeds the
country-specifi c grid overvoltage limit value, the inverter switches off .
›
Ensure that the conductor cross-sections are suffi ciently large or that the cable lengths are suffi -
ciently short.
NOTE
In order to avoid asymmetries in the grid, systems with multiple inverters should be designed so that
the inverters feed into the grid in diff ering phases.
›
The dynamic grid support (FRT) only functions with a three-phase grid connection.
›
Observe the following grid-type-specifi c connection requirements and the schematic view in sec-
tion 3.2.3 on page 9.
Country and
Grid monitoring
grid-type
Three-phase or
DE
NSp.
single phase
IT
Single-phase
Three-phase or
other countries
single phase
Table 5:
Grid-type-specifi c connection conditions
ACTIVITY
Cables on the AC screw terminal must be re-tightened at regular intervals using the necessary
tightening torque (see chapter 7.2 on page 21).
Operating Instructions for Powador 2002-6002_EN
Conductor cross-section
1.5 mm²
2.5 mm²
4.0 mm²
4.0 mm²
6.0 mm²
Fuse protection: gL safety fuses
16 A for 1.5 mm² conductor cross-section
20 A for 2.5 mm² conductor cross-section
25 A for 4.0 mm² conductor cross-section
25 A for 4.0 mm² conductor cross-section
35 A for 6.0 mm² conductor cross-section
Required
monitoring
phase unbalanced load
phase unbalanced load 6 kVA
If you have any queries, please contact your grid operator.
max. asymmetry between
phases L1,L2,L3
4.6 kVA
Page 23