Configuration and Operation
Authorised electrician
Country-spec.
Menu
Setting
level
1
2
3
3
ES P.O. 12.3,
ES RD 661, ES
RD 1699, UD,
IT-CEI021,
GB-G59
1
2
3
3
1
2
3
3
DE NSp,
1
2
3
3
All countries
1
2
3
3
All countries
1
2
3
3
1
2
3
3
All countries
1
2
3
3
BE, DE
IT
Page 40
Display/
setting
Minimum
grid frequency
Maximum
grid frequency
Minimum/
maximum grid
frequency
Minimum/
maximum grid
frequency
Starting voltage
Grnd fl t monitor
Internal power
limiting
Reactive power
setting
Action in this menu/meaning
The inverter monitors the grid frequency continuously.
If the grid frequency exceeds or drops below the confi g-
ured values, the inverter switches off .
Set limit values for fast and slow underfrequency
shutdown in 0.1 Hz increments
Enter the shutdown threshold for fast and slow over-
voltage shutdown.
Set limit values for fast and slow underfrequency
shutdown in 0.1 Hz increments
Enter the shutdown threshold for fast and slow over-
frequency shutdown.
Shows the minimum/maximum allowable grid fre-
quency.
Shows the minimum/maximum allowable grid fre-
quency.
Set limit values for underfrequency and overfre-
quency switch-off in 0.1 Hz increments
The inverter begins feed-in as soon as this PV voltage is
present.
Set the starting voltage.
One pole of the PV generator is grounded in the unit
using a fuse. Ground fault monitoring is triggered in the
event of an ground fault in the generator. This prevents
possible damage to the modules.
NOTE:
Activate ground fault monitoring only if you have
grounded one pole of the PV generator.
(See section 7.3 on page 40)
Activate or deactivate the ground fault monitoring
function.
The power reduction function is password-protected.
Power is reduced in 10 W steps and is limited to 50% of
the nominal unit power.
Enter the four-digit password using key "2".
Set power limiting.
Password protection can be re-activated.
The following control methods can be set. At least one
mode must be active.
Q specifi cation
cos phi specifi cation
cos phi(P/Pn)
Q(U) characteristic
Characteristic Q=f(U) - activate 5 nodes from value
pairs (Q1:U1 – Q5:U5).
Characteristic Q=f(U) - activate two-state controller
with 4 fi xed value pairs (Q:U).
Operating Instructions for Powador 2002-6002_EN