Configuration and Operation
Authorised electrician
Country-spec.
Menu
Setting
level
1
2
3
3
All countries
1
2
3
3
ES P.O. 12.3,
ES RD 661, ES
RD 1699, HU,
IN, IT, UD
DE, DE-VD-
N,BE
1
2
3
3
BG, CZ, FR
BG, CZ, FR ,PF
1
2
3
3
BG, CZ, FR ,
PF, DE, DE-
1
2
3
3
VDN, BE
DK, GR-(M/I),
1
2
3
3
GB-G83, IL,
PT, KR, SI
Operating Instructions for Powador 2002-6002_EN
Display/
setting
"Parameters" menu
Selecting country
with grid type and
directive
Overvoltage
shutdown
Max. line voltage
EN 50160
Voltage drop
between meter and
inverter
Line undervolt-
age/overvoltage
switch-off
Action in this menu/meaning
Only service technicians are permitted to make changes
in the parameter menu.
↻ You are in menu level "1".
↻ The unit name is displayed.
 Press "2" for at least 15 seconds to run through menu
level 3.
The default setting is used if "no" is selected.
1.
Enter the four-digit password using key "2". The pass-
word is unit-specifi c.
2. Confi rm what you have entered using key "1".
3. Set the desired country setting.
 Select the type of grid applicable to the use of the
inverter.
NOTE: This option infl uences the country-specifi c operat-
ing settings of the inverter. Please consult KACO service
for further information.
 Specify the shutdown threshold for fast and slow
overvoltage shutdown.
 Set period from occurrence of the fault to shutdown
of the inverter.
 Activate or deactivate password protection.
 Specify the shutdown threshold for overvoltage
shutdown.
The 10-minute average for the measured voltage as
per EN50160 is used.
 Set period from occurrence of the fault to shutdown
of the inverter.
 Specify the shutdown threshold for overvoltage
shutdown.
The 10-minute average for the measured voltage as
per EN50160 is used.
 Set period from occurrence of the fault to shutdown
of the inverter.
The grid voltage is averaged over ten minutes. If the
defi ned value is exceeded, the inverter is disconnected
from the grid.
 Set voltage threshold.
The voltage drop between the inverter and the grid-feed
meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can be
set from 0 to 11 V in 1 V increments.
 Specify the switch-off value for the voltage drop
(0 to 11 V).
The inverter is equipped with redundant 3-phase moni-
toring. If the grid frequency exceeds or drops below the
confi gured values, the inverter switches off . The mini-
mum switch-off threshold can be set in 1 V increments.
 Confi gure the switch-off values for undervoltage and
overvoltage.
Page 39