Startup Polls; Polls To Remote Modules; Mappings From Wi-Gtwy-9; Modules - Weidmuller WI-GTWY-9 User Manual

Wireless gateway
Table of Contents

Advertisement

WI-GTWY-9-xxx Wireless Gateway

4.4.4 Startup Polls

You can enter start up polls for remote modules by using the "New Poll Mapping" box. This
function is the same as for the WI-I/O 9-x I/O modules. A start-up poll is a special message sent
when the WI-GTWY-9-xxx starts up. When the remote module receives a start-up poll, it will
immediately respond with update messages for all its inputs that are mapped to the WI-GTWY-9-
xxx. This allows the WI-GTWY-9-xxx to have correct values on start-up.

4.4.5 Polls to Remote Modules

It is possible for a WI-GTWY-9-xxx to send a poll to a remote module at other times apart from
start-up. A poll can be sent under the following events:
• based on a configurable time period
• based on real time clock
• on-demand by the host device.
For information on this configuration, refer to the next section on "Block Mappings".
4.5 Mappings from WI-GTWY-9-xxx to other WI-GTWY-9-
xxx Modules
Individual links between WI-GTWY-9-xxx modules can be configured under the "Mappings"
selection as described in the previous section. For example, if you want to transfer I/O Reg 144
in WI-GTWY-9-xxx#2 to I/O Reg 286 in WI-GTWY-9-xxx#3, you can enter the following
mapping:
Whenever I/O Reg 144 changed by the sensitivity amount, WI-GTWY-9-xxx#2 would send a
message to WI-GTWY-9-xxx#3 to write the value in I/O Reg 286. The problem arises if there
are a lot of these mappings. Each radio message only relates to one register-register link. If you
want to map 1000 registers from one WI-GTWY-9-xxx to another, then this could generate a lot
of radio messages.
V1.18
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wi-gtwy-9-xxx series

Table of Contents