Profibus Slave Indicating Led's - Weidmuller WI-GTWY-9 User Manual

Wireless gateway
Table of Contents

Advertisement

WI-GTWY-9-xxx Wireless Gateway

6.4.2 Profibus Slave Indicating LED's

LED No
Indication
1
-
2
Green
2
Off
3
Red
3
Off
4
Flashing Red 1
Hz
4
Flashing Red 2
Hz
4
Flashing Red 4
Hz
4
Off
LED n
Description
Not Used
Module is On-Line and data exchange is possible.
Module is not On-Line
Module is Off-Line and no data exchange is possible.
Module is not Off-Line
Error in configuration: IN and/or OUT length set during
initialization of the module is not equal to the length set during
configuration of the network.
Error in User Parameter data: The length/contents of the User
Parameter data set during initialization of the module is not equal
to the length/contents set during configuration of the network.
Error in initialization of the Profibus communication ASIC.
No diagnostics present
V1.18