WI-GTWY-9-xxx Wireless Gateway
Parameter
Area
Offset
Type
Match Value
Mask
Match
Operand
Recipient(s)
Sender
Subject line
Extra Headers
Message Body
The data is read in the Fieldbus Interface from the area and offset specified by the
parameters Area, and Offset. The data size to read is specified by the Type parameter. The
module performs a logical 'AND' between the read data and the parameter Mask. The
result is compared with the parameter Match Value. How the data shall be compared is
specified by the Match Operand.
Example:
[Register]
IN, 0x0003, byte
[Register match]
0x20, 0x7F, >
[To]
support@weidmuller.com
[From]
TEST@weidmuller.com
[Subject]
Status
[Message]
All data correct.
In the above example:
• A byte is read from the Fieldbus IN area, at byte address 0003h
• The module performs a logical <data> AND 7Fh.
• If the result is larger than 20h, the email message is sent to
support@weidmuller.com
Description
Source Fieldbus Interface Area. Possible values are 'IN' or 'OUT'
Source offset in Fieldbus Area, shall be written in decimal or hexadecimal.
Source data type. Possible values are 'byte', 'word', and 'long'
Value to compare with the source data. Shall be written in decimal or
hexadecimal.
The module performs a logical 'and' on the source data and this Mask before
the value is compared with the Match Value. The value shall be written in
decimal or hexadecimal.
Specifies how the data shall be compared with the Match Value. Possible
values: '<', '=', '>'
Destination email addresses, semicolon separated
Sender email address
Email subject (One line only)
Optional. May be useful for advanced users when for example sending HTML
emails etc.
The actual email message.