WI-GTWY-9-xxx Wireless Gateway

6.4 Fieldbus Indicating LEDs

All WI-GTWY-9-xxx modules (except MD1) are equipped with four fieldbus indication LED' s
located in the module end plate, used for diagnostics purposes. The meaning of the LED's for
each fieldbus is described below.

6.4.1 Ethernet Indicating LED's

The WI-GTWY-9-ET1 module can communicate Modbus TCP or EtherNet IP
based protocols. The LED sequence will vary depending on Protocol being used and Ethernet
Board firmware.
Changes to Ethernet Board firmware effect LED 2 indications when flashing. When flashing this
only indicates that an EtherNet IP connection has not been made to the WI-GTWY-9-ET1.
Example would be RSLogix has not had a Generic Ethernet Device added with WI-GTWY-9-
ET1 IP address and connection data.
If using Modbus TCP then LED's 2 & 3 have no function in regards to the Modbus TCP
communications of the module
LED no
Color
1
Green
2
Green
2
Green
2
Green
2
Red
2
Red
2
Green/Re
d
3
Green
3
Green
3
Green
3
Red
3
Red
3
Green/Re
d
4
Green
150
State
Description
-
The Link LED indicates that the module is connected to an
Ethernet network.
Off
No power applied to module.
Steady
Device operating correctly.
Flashing
Module configured, Scanner in Idle State (EtherNet IP only)
Flashing
Minor recoverable fault has been detected.
Steady
Major internal error has been detected.
Flashing
Power on self-test.
Off
No power applied or no IP address has been assigned.
Steady
Module has at least one Ethernet/IP connection established.
Flashing
No Ethernet/IP connections to the module.
Flashing
Connection timeout
Steady
Duplicate IP address
Flashing
Power on self-test.
Flashing
Flashes each time a packet is received or transmitted.
V1.18