Weidmuller WI-GTWY-9 User Manual page 125

Wireless gateway
Table of Contents

Advertisement

WI-GTWY-9-xxx Wireless Gateway
Modbus/TCP Addressing
The IN and OUT areas of the Ethernet interface are addressed under Modbus/TCP according to
the tables below. Since Modbus uses a 16-bit format, "Word (16-bit) Address Mode" will be
automatically applied whenever the "Modbus/TCP" checkbox is checked. If Ethernet/IP is also
enabled, the "Disable I/O Instance" option must be selected for each fieldbus mapping to which
Modbus/TCP Addressing is to apply.
IN Area Modbus TCP Addresses (WI-GTWY-9-xxx Write Locations 0 – 1023*)
IN
Modbus
Area
Word
Location
Address
0
1
1
2
---
---
1022
1023
1023
1024
OUT Area Modbus TCP Addresses (Fieldbus READ Locations 0 – 1023*)
OUT
Modbus
Area
Word
Location
Address
0
1025
1
1026
---
---
1022
2047
1023
2048
* Assumes Word Mode Addressing is selected in Configuration Software
The Fieldbus IN and OUT areas can be configured to a maximum size of 1024 words (2048
bytes) each, depending on the configured fieldbus mappings. The highest mapped location will
correspond to the highest available Modbus register (or coil) available to a Modbus/TCP client.
A Modbus/TCP client must use the appropriate Modbus Coil or Modbus Word addresses
corresponding to configuration software, as well as the correct function code (see 4.12.2
Supported Commands).
Modbus Bit Address
Bit 15
Bit 14
Bit 13
1
2
3
17
18
19
---
---
---
16353
16354
16355
16369
16370
16371
Modbus Bit Address
Bit 15
Bit 14
Bit 13
16385
16386
16387
16401
16402
16403
---
---
---
32737
32738
32739
32753
32754
32755
---
Bit 2
Bit 1
---
14
15
---
30
31
---
---
---
---
16382
16383
---
16382
16383
---
Bit 2
Bit 1
---
16398
16399
---
16414
16415
---
---
---
---
32750
32751
---
32766
32767
V1.18
Bit 0
16
32
---
16384
16384
Bit 0
16400
16416
---
32752
32768
125