Replacing An Ebm - Eaton Powerware 9910 UPS Installation Manual

6000 va models for ibm applications
Table of Contents

Advertisement

Four IEC 320−C19
Output
receptacles
circuit
(Load segment 1)
breakers
EBM connector
Output
circuit breaker

Replacing an EBM

Communication
bay
Six IEC 320−C13
receptacles (Load segment 2)
Figure 2. The 9910-E67 UPS Rear Panel
Follow the steps in this section if you are replacing an existing, installed
EBM with a new EBM. If you are installing a new UPS or EBM, continue
to "Rack Installation and UPS Internal Battery Connection" on page 21.
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
An EBM can be replaced easily without turning the UPS off or
disconnecting the load.
If you prefer to remove input power to replace the EBM:
1.
Press and hold the on/off button until the long beep ceases
(approximately 3 seconds), and then disconnect the UPS.
2.
Wait 60 seconds while the internal processor shuts down before
you disconnect the EBM.
Eaton 9910 UPS and EBM Installation Guide (6000 VA Models)
L6−30
P
inlet
connector
L6−30 P
Fan
USB
REPO
connector
S
P-164000007 Rev 1
INSTALLATION
RS−232
connector
Ground
screw
19