Vitotronic 300, GW5B Installation and Service

"Boiler" Group

Coding in the delivered condition
0C:0
Do Not Adjust
1F:0
With flue gas temperature sensor:
Flue gas temperature is not monitored for
service display.
21:0
No service interval (hours run) selected.
23:0
No interval for service.
24:0
No "Service" display.
28:0
No burner interval ignition.
2D:...
Delivered condition defaulted by the boiler
coding card.
Do Not Adjust

"DHW" Group

Coding in the delivered condition
55:0
DHW tank heating, hysteresis ± 2.5 K.
56:0
Set DHW temperature adjustable from
50 to 140°F (10 to 60°C).
58:0
Without auxiliary function for DHW heating.
Possible change
--
1F: 34 (1)
When the limit for the flue gas temperature is
to
exceeded,
1F: 482°F
(250°C)
21:1
The number of hours run before the burner
to
should be serviced is adjustable from
21:100
100 to 10,000 h; 1 step ≙ 100 h
23:1
Interval adjustable from 1 to 24 months.
to
23:24
24:1
"Service" display (the address is automatically
set and must be manually reset after a service
has been carried out).
28:1
Time interval adjustable from 1 to 24 h. Burner
to
is force-started for 30 sec. respectively.
28:24
--
Possible change
55:1
Adaptive DHW tank heating enabled
(see page 54).
55:2
DHW tank temperature control with 2 DHW
tank temperature sensors.
55:3
DHW tank temperature control, primary store
system.
56:1
Set DHW temperature adjustable from
50 to 203°F (10 to 95°C).
Note: Observe the max. permissible DHW
temperature. Change setting of
temperature controller "
58:10
Input of a second set DHW temperature,
to
adjustable from 50 to 203°F (10 to 95°C)
58:60
(observe coding address "56" in this group).
Code 2
--
is displayed.
--
R
".
69