Code 2
"General" Group
Coding in the delivered condition
2E:0
Without wireless outside temperature sensor.
2F:0
Do Not Adjust
30:0
Without plug-in adaptor 1 for external safety
equipment.
31:0
Without plug-in adaptor 2 for external safety
equipment.
32:0
Do Not Adjust
40:...
Servomotor runtime at plug gSA1. Delivered
condition defaulted by boiler coding card.
4A:0
Sensor aJA not fitted.
4B:0
Sensor aJB not fitted.
4C:0
Connection on plug sÖA1: Delivered condition
defaulted by the boiler coding card.
4D:1
Connection at plug sL:
Shunt pump.
(adjust to 4D:2)
4E:...
Connection on plug gSA1: Delivered condition
defaulted by the boiler coding card.
4F:...
Do Not Adjust
52:0
Without supply temperature sensor for low loss
header.
53:1
With low loss header: Boiler circuit pump only
runs when there is demand if the burner is
operational (with run-on time).
54:0
Without solar thermal system.
5B:0
Without extension EA1.
5C:0
Function, output aBJ at extension EA1:
Central fault message.
64
(continued)
Vitotronic 300, GW5B Installation and Service
Possible change
2E:1
With wireless outside temperature sensor;
automatic recognition. Not used, don't adjust.
2E:2
Wireless outside temperature sensor not used,
don't adjust.
--
30:1
With plug-in adaptor 1 for external safety
equipment; automatic recognition.
31:1
With plug-in adaptor 2 for external safety
equipment; automatic recognition.
--
40:5
Runtime adjustable from 5 to 199 sec.
to
40:199
4A:1
Sensor aJA fitted; automatic recognition.
4B:1
Sensor aJB fitted; automatic recognition.
4C:1
Primary pump, primary store system.
4D:2
Boiler circuit pump.
4D:3
Boiler circuit pump with isolation valve function.
4E:2
Motor for 3-way mixing valve, primary store
system.
--
52:1
With supply temperature sensor for low loss
header; automatic recognition.
53:0
Boiler circuit pump always runs when there is
demand.
54:1
With Vitosolic 100; automatic recognition.
54:2
With Vitosolic 200; automatic recognition.
54:3
With solar control module, type SM1, without
auxiliary function; automatic recognition.
54:4
With solar control module, type SM1, with
auxiliary function, e.g. central heating
backup; automatic recognition.
5B:1
With extension EA1; automatic recognition.
5C:1
Accessories pump.
5C:2
No function.
5C:3
Heating circuit pump A1 is switched to low
speed (reduced mode).
5C:4
Heating circuit pump M2 is switched to low
speed (reduced mode).
5C:5
Heating circuit pump M3 is switched to low
speed (reduced mode).
--
--
--