Vitotronic 300, GW5B Installation and Service
"Heating circuit 1", "Heating circuit 2", "Heating circuit 3" Group
Coding in the delivered condition
A4:0
With frost protection.
A5:5
With heating circuit pump logic function
(economy mode): heating circuit pump "OFF"
when the outside temperature (AT) is 1 K
higher than the set room temperature (RTset)
AT > RTset + 1 K.
Parameter address
A5:...
1
2
3
4
5
6
7
to
15
Coding in the delivered condition
A6:36
Extended economy mode disabled.
A7:0
Only for heating circuits with mixing valve:
Without mixing valve economy function.
A9:7
With pump idle time
(heating circuit pump"OFF")
(see function description on page 51).
Note: The max. idle period is 10 h.
AA:2
With output reduction by temperature
sensor aJA.
With heating circuit pump logic function: Heating circuit pump "OFF"
AT > RTset + 5 K
AT > RTset + 4 K
AT > RTset + 3 K
AT > RTset + 2 K
AT > RTset + 1 K
AT > RTset
AT > RTset – 1 K
AT > RTset – 9 K
Possible change
A4:1
No frost protection; this setting is only possible
if code "A3:– 9" has been selected.
Note: Information regarding coding address
"A3" should be observed.
A5:1
With heating circuit pump logic function:
to
Heating circuit pump "OFF";
A5:15
see the following table.
Possible change
A6:5
Extended economy control enabled,
to
i.e. the burner and heating circuit pump will
A6:35
stop and the mixing valve will be closed at a
variable value, adjustable between 41 to 95°F (5
and 35°C) plus 34°F (1°C). The base value is the
adjusted outside temperature. This value is based
on the actual outside temperature and a time
constant, which takes the cooling down of an
average building into consideration.
A7:1
With mixing valve economy function (extended
heating circuit pump logic): Heating circuit pump
also "OFF":
If the mixing valve has been closed for longer
than 12 min.
Heating circuit pump "ON":
If the mixing valve changes to control function.
If there is a risk of frost.
A9:0
Without pump idle time.
A9:1
With pump idle time, adjustable from 1 to 15.
to
1 = short idle period
A9:15
15 = long idle time
AA:0
Without output reduction.
AA:1
No function.
Code 2
(continued)
75