Viessmann Vitotronic 300 Installation And Service Instructions Manual page 72

Type gw5b, vitotronic 300, type gw5b weather-compensated, digital boiler control unit for boiler model cm2 - 400, 500, 620 and 620 tx
Table of Contents

Advertisement

Code 2
Calling up coding level 2
"Solar" Group
Coding in the delivered condition
06:75
Maximum speed of the solar circuit pump
75% of the maximum possible speed.
07:0
Interval function of the solar circuit pump
switched off.
08:60
Set DHW temperature (maximum DHW
tank temperature) 140°F (60°C).
09:130
Maximum collector temperature (to protect
the system components) 266°F (130°C).
0A:5
Temperature differential for stagnation
time reduction (reduction in the speed of
the solar circuit pump to protect system
components and heat transfer medium) 5 K.
0B:0
Frost protection function for solar circuit
switched off.
0C:1
n
t monitoring switched on. No flow rate
captured in the solar circuit, or flow
rate too low.
0D:1
1 Night circulation monitoring switched on.
Unintentional flow rate is captured in the
solar circuit (e.g. at night).
0E:1
Heat statement in conjunction with
Viessmann heat transfer medium.
0F:70
Solar circuit flow rate at the maximum
pump speed 7 L/min.
10:0
Target temperature control switched off
(see coding address "11").
11:50
Set solar DHW temperature 122°F (50°C).
Target temperature control switched on
(code "10:1"): Temperature at which
the solar heated water in the DHW
DHW tank is to be stratified.
Code "20:9" (heating of two DHW
DHW tanks) is selected: When one DHW
DHW tank reaches its set DHW
temperature, the second DHW tank is
heated.
72
(continued)
Vitotronic 300, GW5B Installation and Service
Possible change
06:1
Maximum speed of the solar circuit pump is
to
adjustable from 1 to 100%.
06:100
07:1
Interval function of the solar circuit pump
switched on. To capture the collector
temperature more accurately, the solar circuit
pump starts for short cycles.
08:10
Set DHW temperature adjustable from
to
50 to 194°F (10 to 90°C).
08:90
09:20
Temperature adjustable from 68 to 392°F
to
(20 to 200°C).
09:200
0A:0
Stagnation time reduction is disabled.
0A:1
Temperature differential adjustable from
to
1 to 40 K.
0A:40
0B:1
Frost protection function for solar circuit
switched on (not required with Viessmann
heat transfer medium).
0C:0
n
t monitoring switched off.
0D:0
Night circulation monitoring switched off.
0E:2
Never adjust.
0E:0
No heat statement.
0F:1
Flow rate adjustable from 1.6 to 404 USG/h
to
(0.1 to 25.5 L/min).
0F:255
1 step ≙ 1.6 USG/h (0.1 L/min)
10:1
Target temperature control switched on.
11:10
The set solar DHW temperature is adjustable
to
from 50 to 194°F (10 to 90°C).
11:90