Viessmann Vitotronic 300 Installation And Service Instructions Manual page 77

Type gw5b, vitotronic 300, type gw5b weather-compensated, digital boiler control unit for boiler model cm2 - 400, 500, 620 and 620 tx
Table of Contents

Advertisement

Vitotronic 300, GW5B Installation and Service
"Heating circuit 1", "Heating circuit 2", "Heating circuit 3" Group
Coding in the delivered condition
B9:0
With remote control unit and for the
heating circuit, operation with room
temperature hook-up must be
programmed:*2
Without learning start optimization.
C0:0
With remote control:*2
Without stop optimization.
C1:0
With remote control:*2
Without stop optimization.
C2:0
With remote control:*2
Without learning stop optimization.
C3:125
Only for heating circuits with mixing valve:
Mixing valve runtime 125 sec.
C4:1
System dynamics:
Mixing valve control characteristics
C5:20
Electronic minimum supply temperature
limit 68°F (20°C) (only in operation with
standard room temperature).
C6:75
Electronic maximum supply temperature
limit set to 168°F (75°C).
C8:31
With remote control unit and for the heating
circuit, operation with room temperature
hook-up must be programmed:*2
No room influence limit.
D5:0
With external heating program changeover
(observe setting of coding address "5D",
"5E", "5F" and "91" in the "General" group):
Heating program switches to "Constant
central heating with reduced room
temperature" or "Standby mode" (subject
to the settings of the set reduced room
temperature).
D8:0
With extension EA1:
No heating program changeover.
*2 Only change the code for the heating circuit without mixing valve A1 for boilers without lower temperature limit
or for the heating circuits with mixing valve if a remote control is connected to them.
Possible change
B9:1
With learning start optimization.
C0:1
With stop optimization, max. setback time delay 1 h.
C0:2
With stop optimization, max. setback time delay 2 h.
C1:1
With stop optimization of setback time delay,
to
adjustable from 10 to 120 min;
C1:12
1 step ≙ 10 min
C2:1
With learning stop optimization.
C3:10
Runtime adjustable from 10 to 255 sec.
to
C3:255
C4:0
Controller responds too quickly (cycles between
to
"Open" and "Close"): Select a lower value.
C4:3
Controller responds too slowly (temperature is not
held sufficiently): select a higher value.
C5:1
Minimum limit adjustable from 34 to 261°F
to
(1 to 127°C) (limited by boiler-specific parameters).
C5:127
Maximum limit adjustable from 50 to 261°F
(10 to 127°C) (limited by boiler-specific
parameters).
C8:1
Room influence limit adjustable from 1 to 30 K.
to
C8:30
D5:1
The heating program changes to "Constant
operation with standard room temperature".
D8:1
Heating program changeover via input DE1.
D8:2
Heating program changeover via input DE2.
D8:3
Heating program changeover via input DE3.
Code 2
(continued)
77