Vitotronic 300, GW5B Installation and Service
"General" Group
Coding in the delivered condition
5D:0
Function input DE1 at extension EA1:
No function.
5E:0
Function input DE2 at extension EA1:
No function.
5F:0
Function input DE3 at extension EA1:
No function.
6C:0
Do Not Adjust
6D:0
Do Not Adjust
6E:50
No display correction of the outside
temperature.
(continued)
Possible change
5D:1
Heating program changeover.
5D:2
External demand with set minimum boiler
water temperature. Setting of the set value
in coding address "9B".
5D:3
External blocking.
5D:4
External blocking with fault message.
5D:5
Fault message input.
5D:6
Brief operation, DHW circulation pump
(pushbutton function). Setting of runtime
for DHW circulation pump in coding
address "12" in the "General" group.
5E:1
Heating program changeover.
5E:2
External demand with set minimum boiler
water temperature. Setting of the set value
in coding address "9B".
5E:3
External blocking.
5E:4
External blocking with fault message.
5E:5
Fault message input.
5E:6
Brief operation, DHW circulation pump
(pushbutton function). Setting of runtime
for DHW circulation pump in coding
address "12" in the "General" group.
5F:1
Heating program changeover.
5F:2
External demand with set minimum boiler
water temperature. Setting of the set value
in coding address "9B".
5F:3
External blocking.
5F:4
External blocking with fault message.
5F:5
Fault message input.
5F:6
Brief operation, DHW circulation pump
(pushbutton function). Setting of runtime for
DHW circulation pump in coding address "12"
in the "General" group.
--
--
6E:0
Display correction –5 K
to
to
6E:49
Display correction –0.1 K
6E:51
Display correction +0.1 K
to
to
6E:99
Display correction +4.9 K
Code 2
--
--
65